January 2007
2007 MASTER FORMAT™ SECTION 08 45 23
(Previously section 08950)
INSULATED TRANSLUCENT FIBERGLASS SANDWICH PANEL SKYLIGHT SYSTEM
PART 1 - GENERAL1.1 SUMMARY
A. Section includes the insulated translucent sandwich panel skylight system as shown and specified. Work includes providing and installing:
A. Submit manufacturer’s product data. Include construction details, material descriptions, profiles and finishes of skylight components.
B. Submit shop drawings. Include plans, details, dimensions and attachments to other work.
C. Submit manufacturer's color charts showing the full range of colors available for factory finished aluminum.
a. Sandwich panels: 14” x 28” units
b. Factory finished aluminum: 5” long sections
E. Submit product test reports from a qualified independent testing
agency indicating each type and class of skylight panel system complies with
the project performance requirements, based on comprehensive testing of current
products. Previously completed test
reports will be acceptable if for current manufacturer and indicative of
products used on this project.
1.3 QUALITY ASSURANCE
A. Manufacturer's Qualifications
1. Test reports required are:
F. Submit current documentation indicating regular, independent quality control monitoring under a nationally recognized building code review and listing program.
a. Flame Spread and Smoke Developed (UL 723) – Submit UL Card
b. Burn Extent (ASTM D-635)
c. Color Difference (ASTM D-2244)
d. Abrasion/Erosion Resistance (ASTM D-4060)
e. Impact Strength (UL 972)
f. Bond Tensile Strength (ASTM C-297 after aging by ASTM D-1037)
g. Bond Shear Strength (ASTM D-1002)
h. Beam Bending Strength (ASTM E-72)
i. Bond Shear Strength (ASTM D-1002)
j. NFRC System Certification
k. Condensation Resistance Factor (AAMA 1503)
l. Class A Roof Covering Burning Brand (ASTM E1O8)
m. UL Listed Class A Roof System (UL 790) (Optional) – Submit UL Card
n. Blast Analysis and Testing of Translucent Sandwich Panels Demonstrating Equivalent Performance to 1/4" Laminated Glass per DoD UPC 4-010-01. (Optional)1. Material and products shall be manufactured by a company continuously and regularly employed in the manufacture of specified materials for a period of at least ten (10) consecutive years and which can show evidence of those materials being satisfactorily used on at least six (6) projects of similar size, scope and
location. At least three (3) of the projects shall have been in successful use
for ten (10) years or longer.
B. Installer’s Qualifications: Installation shall be by an experienced installer, which has been in the business of installing specified skylight systems for at least five (5) consecutive years and can show
evidence of satisfactory completion of projects of similar size, scope and
type.
2. Skylight system must be
listed by the International Code Council – Evaluation Service (ICC-ES)
which requires quality control inspections and fire, structural and water
infiltration testing of sandwich panel systems by an approved agency.
3. Quality control inspections and required testing shall be conducted at least once each year and shall include manufacturing facilities, sandwich panel components and production sandwich panels for conformance with “Acceptance Criteria for Sandwich Panels” as regulated by the ICC-ES.
C. Performance Requirements: The manufacturer shall be responsible for the configuration and fabrication of the complete skylight panel system.
A. Deliver skylight system, components and materials in manufacturer's standard protective packaging.
B. Store skylight panels on the long edge, several inches above the ground, blocked and under cover in accordance with manufacturer's storage and handling instructions.
1.5 WARRANTY
A. Submit manufacturer's and installer's written warranty agreeing to repair or replace skylight system work which fails in materials or workmanship within one (1) year of the date of delivery. Failure of materials or workmanship shall include leakage, excessive deflection, deterioration of finish on metal in excess of normal weathering and defects in accessories, insulated translucent sandwich panels and other components of the work. (Contact local representative for extended warranty periods.)
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Kalwall Corporation, tel: (800) 258-9777
B. Structures Unlimited, Inc., tel: (800) 225-3895
2.2 PANEL COMPONENTS
A. Face Sheets
a. Thermoplastic (e.g. polycarbonate, acrylic) faces are not acceptable.
a. Flamespread: Underwriters Laboratories (UL) listed, which requires periodic unannounced retesting, with flamespread rating no greater than 50 (20) and smoke developed no greater than 250 (200) when tested in accordance with UL 723.
b. Burn extent by ASTM D-635 shall be no greater than 1”.
c. Face sheets shall not deform, deflect or drip when subjected to fire or flame.
d. Face sheets shall not delaminate when exposed to 200°F for 30 minutes per IBC and NBC (300°F for 25 minutes per UBC and SBC).
a. Color stability: Full thickness of the exterior face sheet shall not change color more than 3.0 (7.0) CIE Units DELTA E by ASTM D-2244 after 5 years (30 months) outdoor South Florida weathering at 5 degrees facing south, determined by the average of at least three (3) white samples with and without a protective film or coating to ensure long-term color stability. Color stability shall be unaffected by abrasion or scratching.
b. Erosion barrier: Exterior face shall have a permanent glass erosion barrier embedded beneath the surface to provide long-term resistance to reinforcing fiber exposure. Exterior face surface loss shall not exceed .7 mils and 40 mgs when tested in accordance with ASTM D-4060 employing CS17 abrasive wheels at a head load of 500 grams for 1000 cycles. Sacrificial surface films or coatings are not acceptable erosion barriers.
a. Exterior face sheets: Smooth, 0.070” thick and _______ in color.
b. Interior face sheets: Smooth, 0.045” thick and _______ in color.
c. Face sheets shall not vary more than +/- 10% in thickness and be uniform in color.
a. 50% Relative Humidity at 73° F: 540 PSI
b. 182° F: 100 PSI
c. Accelerated Aging by ASTM D-1037 at room temperature: 800 PSI
d. Accelerated Aging by ASTM D-1037 at 182° F: 250 PSI
e. 500 Hour Oxygen Bomb by ASTM D-572: 1400 PSI
A. Provide sandwich panels of flat fiberglass reinforced translucent face sheets laminated to a grid core of mechanically interlocking thermally broken (aluminum) I-beams. The adhesive bonding line shall be straight, cover the entire width of the I-beam and have a neat, sharp edge.
a. Complete insulated panel system shall have NFRC certified U-factor of _____.
C. Panels shall withstand 1200ºF fire for minimum one (1) hour without collapse or exterior flaming.
D. Thermally broken panels:
2.4 BATTENS AND PERIMETER CLOSURE SYSTEMS
A. Closure system: Extruded aluminum 6063-T6 and 6063-T5 alloy and temper clamp-tite screw type closure system. (Curved closure system may be roll formed.)
C. Fasteners: 300 series stainless steel screws for aluminum closures, excluding final fasteners to the building.
D. Finish: Exposed aluminum to be manufacturer’s factory applied finish that meets the performance requirements of AAMA 2604. (Mill)
3. EXAMINATION
A. Examine substrates, supporting structure and installation conditions. Do not proceed with skylight erection until unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Metal Protection:
A. Install the skylight system in accordance with the manufacturer's installation recommendations and approved shop drawings.
1. Anchor component parts securely in place by permanent mechanical
attachment system.
2. Accommodate thermal and mechanical movements.
3. Set sill and curb members in a full bed of sealant compound, or with joint fillers or gaskets to provide weather-tight construction.
B. Install joint sealants at perimeter joints and within the skylight system in accordance with manufacturer's installation instructions.
3.4 FIELD QUALITY CONTROL
A. Water Test: Test skylights according to procedures in AAMA 501.2.
B. Repair or replace work that does not pass testing or that is damaged by testing and retest work.
3.5 CLEANING
A. Clean the skylight system inside and outside, immediately after installation, according to manufacturer's written recommendations.